Yayın:
Power Quality Assessment of Indoor LED Luminaires

Yükleniyor...
Küçük Resim

Tarih

Kurum Yazarları

Danışman

item.page.editor

Editör

Bölüm / Program

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

IEEE

DOI

10.1109/pq.2019.8818234
View PlumX Details

Araştırma Projeleri

Akademik Birimler

Dergi Sayısı

Özet

Due to the fact that it is a semiconductor based lighting equipment, the LEDs have important effects on the power quality. In the ever-expanding lighting industry, the use of LED equipment is increasing day by day. Therefore, it is very important to analyze and interpret the effects of LEDs on the grid. In this study, power quality measurements of 4 different commercial LED luminaires have been realized and the results obtained have been interpreted. According to the measurements, it is found that the power factor values are acceptable for the luminaries when they are completely on. However, when the luminaries are dimmed, it has been observed that the power factor decreased and the current harmonics exceeded the limit values determined by the related standards. On the other hand, it is seen that all the luminaires provide flicker boundaries. As a result of the study, it has been concluded that the effects of dimmable equipment on power quality should be analyzed in more detail.

Tanım

Dergi veya Seri

2019 ELECTRIC POWER QUALITY AND SUPPLY RELIABILITY CONFERENCE (PQ) & 2019 SYMPOSIUM ON ELECTRICAL ENGINEERING AND MECHATRONICS (SEEM)

ISSN

ISBN

978-1-7281-2650-0

Haklar

Alıntı

Koleksiyonlar

Onay

Gözden geçir

Tamamlayıcı Bilgiler

Referans Gösteren

Related Patent

Related Goal

0

Views

0

Downloads