Yayın: EFFECTS OF VARYING INLET IRON AND MANGANESE CONCENTRATIONS ON SLOW SAND FILTER PERFORMANCE
Yükleniyor...
Tarih
Danışman
item.page.editor
Editör
Bölüm / Program
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
YILDIZ TECHNICAL UNIV
DOI
Türü
Özet
In this study a laboratory-scale slow sand filter (SSF) is used for removal of iron and manganese and the effects of various inlet concentrations on removal efficiency were investigated. SSF was operated at a filtration rate of 0.2 m.h(-1) with two different synthetic inlet waters (Run1 and Run2). Iron and manganese concentrations in two runs were 1.09 +/- 0.13mg. L-1-1.06 +/- 0.10 mg.L-1 for Run1 and 2.02 +/- 0.15 mg.L-1-2.10 +/- 0.14 mg.L-1 for Run2. In Run1, the removal efficiencies of 96.3 +/- 2.48%, 92.3 +/- 6.1%, 92.6 +/- 5.7%, and 55.3 +/- 8.3% were obtained for turbidity, iron, manganese and total organic carbon (TOC), respectively. In Run2, on the other hand, the removal efficiencies were obtained as 97.9 +/- 1.3%, 93.1 +/- 8.1%, 94.4 +/- 5.8%, and 55.5 +/- 6.8%, respectively. Results suggested that the SSF was the most efficient in turbidity removal at a filtration rate of 0.2 m.h(-1). Sequence analyses of DGGE bands from Run1 and Run2 were also performed and results indicated that a range of bacteria were present, with 16S rRNA gene sequences similar to groups such as Gallionella, Leptothrix, Crenothrix, and an uncharacterized environmental clone.
Tanım
Dergi veya Seri
SIGMA JOURNAL OF ENGINEERING AND NATURAL SCIENCES-SIGMA MUHENDISLIK VE FEN BILIMLERI DERGISI
ISSN
1304-7205