Yayın:
Energetic and exergetic analysis of optimum insulation thickness for cold storages

dc.contributor.authorKurekci, Nuri Alpay
dc.contributor.authorEmanet, Ozlem
dc.date.accessioned2026-06-27T14:39:22Z
dc.date.issued2022
dc.description.abstractIn this study, the optimum insulation thickness of cold storage walls was calculated energetically and exergetically for five selected insulation materials, whose payback periods were calculated and compared. The effect of each material's unit volume price on the optimum insulation thickness and payback period was also examined. The values of the optimum insulation thickness for polyurethane, extruded polystyrene, rock wool, glass wool, and expanded polystyrene are 2.35-8.43 cm, 5.01-16 cm, 5.81-18.76 cm, 8.10-24.40 cm, and 9.28-28.08 cm, respectively, based on energetic analysis, and 0.08-7.73 cm, 0.91-14.74 cm, 0.97-17.26 cm, 2.01-22.52 cm, and 2.26-25.91 cm, respectively, based on exergetic analysis.en
dc.description.urihttps://doi.org/10.1504/ijex.2022.125526
dc.identifier.doi10.1504/ijex.2022.125526
dc.identifier.eissn1742-8300
dc.identifier.endpage231
dc.identifier.issn1742-8297
dc.identifier.issue2
dc.identifier.startpage215
dc.identifier.urihttps://hdl.handle.net/20.500.14981/63161
dc.identifier.volume39
dc.identifier.wos000853402700006
dc.language.isoeng
dc.publisherINDERSCIENCE ENTERPRISES LTD
dc.relation.ispartofINTERNATIONAL JOURNAL OF EXERGY
dc.subjectoptimum insulation thickness
dc.subjectcold storage
dc.subjectenergy saving
dc.subjectthermo-economic analysis
dc.subjectexergetic analysis
dc.subjectcooling degree-day value
dc.subjectBUILDING WALLS
dc.subjectTHERMAL PERFORMANCE
dc.subjectCOST
dc.subjectThermodynamics
dc.subjectEnergy & Fuels
dc.titleEnergetic and exergetic analysis of optimum insulation thickness for cold storages
dc.typeArticle
dspace.entity.typePublication
local.import.sourceWOS

Dosyalar