Yayın:
Thermal design of Earth-to-Air Heat Exchanger: Performance analysis of new transient semi-analytical model for short period of continuous operation

dc.contributor.authorMelhegueg, Mohammed -Amin
dc.contributor.authorBenchabane, Adel
dc.contributor.authorRouag, Amar
dc.contributor.authorMehdid, Charaf-Eddine
dc.contributor.authorDemir, Hakan
dc.contributor.authorSevindir, Mustafa Kemal
dc.contributor.authorKheireddine, Mohamed-Abdelbassit
dc.date.accessioned2026-06-27T14:41:43Z
dc.date.issued2022
dc.description.abstractThis paper concerns the thermal design of Earth-to-Air Heat Exchanger (EAHE). The paper pre-sents new transient semi-analytical models to estimate i) the disturbed soil thermal resistance of EAHE pipe as a function of duration of operation and ii) thermal performance of EAHE operating under transient conditions. The main aim of this study is to evaluate the parameter choices of this new model for short period of continuous operation of the system (less than 70 h). The results show that time discretization steps of 15 min and 1 h present and lead to appreciable results compared to the experiments. Therefore, the variation of the layer length step of the buried pipe does not alter simulation results. In terms of precision of the soil temperature profile, refined solutions were obtained by the decreasing of the disturbed soil radius and the increasing the number of roots of Bessel's functions. Furthermore, the effect of the variation of surrounding soil radius is discussed for short period of continuous operation of the system. The time step of 1 h and the interval of the surrounding soil radius of 0.4 m-1.1 m are found accurate for good results with a reasonable computational time.en
dc.description.sponsorshipDirectorate General of Scientific Research and Technological Development (DGRSDT)
dc.description.sponsorshipMinistry of Higher Education and Scientific Research, Algeria [A11N01UN070120220002]
dc.description.urihttps://doi.org/10.1016/j.csite.2022.102580
dc.identifier.doi10.1016/j.csite.2022.102580
dc.identifier.issn2214-157X
dc.identifier.urihttps://hdl.handle.net/20.500.14981/63619
dc.identifier.volume40
dc.identifier.wos000891869900008
dc.language.isoeng
dc.publisherELSEVIER
dc.relation.ispartofCASE STUDIES IN THERMAL ENGINEERING
dc.rightsopenAccess
dc.subjectEarth-to-air heat exchanger
dc.subjectTransient semi-analytical model
dc.subjectShort period of continuous operation
dc.subjectPerformance analysis
dc.subjectEATHE SYSTEM
dc.subjectINTERMITTENT
dc.subjectRECOVERY
dc.subjectSATURATION
dc.subjectThermodynamics
dc.titleThermal design of Earth-to-Air Heat Exchanger: Performance analysis of new transient semi-analytical model for short period of continuous operation