Yayın:
Two-phase friction factor in vertical downward flow in high mass flux region of refrigerant HFC-134a during condensation

dc.contributor.authorDalkilic, A. S.
dc.contributor.authorLaohalertdecha, S.
dc.contributor.authorWongwises, S.
dc.contributor.institutionauthorDALKILIÇ, Ahmet Selim
dc.date.accessioned2026-06-27T13:08:21Z
dc.date.issued2008
dc.description.abstractThe two-phase pressure drop of the pure refrigerant HFC-134a during condensation inside a vertical tube-in-tube heat exchanger was investigated. The double tube test section was 0.5 m long with refrigerant flowing in the inner tube and cooling water flowing in the annulus. The inner tube was constructed from smooth copper tubing of 8.1 mm inner diameter and 9.52 mm outer diameter. The test runs were performed at average condensing temperatures of 40-50 degrees C. The mass fluxes were between 260 and 515 kg m(-2) s(-1) and the heat fluxes between 11.3 and 55.3 kW m(-2). The quality of the refrigerant in the test section was calculated using the temperature and pressure obtained from the experiment. The pressure drop across the test section was directly measured by a differential pressure transducer. A new correlation for the two-phase friction factor of R134a flow is proposed by means of the equivalent Reynolds number model. The effects of heat flux, mass flux and condensation temperature on the pressure drop are also discussed. (C) 2008 Published by Elsevier Ltd.en
dc.description.sponsorshipDepartment of Mechanical Engineering, King Mongkut's University of Technology Thonburi (KMUTT)
dc.description.sponsorshipThailand Research Fund (TRF)
dc.description.urihttps://doi.org/10.1016/j.icheatmasstransfer.2008.06.002
dc.identifier.doi10.1016/j.icheatmasstransfer.2008.06.002
dc.identifier.eissn1879-0178
dc.identifier.endpage1152
dc.identifier.issn0735-1933
dc.identifier.issue9
dc.identifier.startpage1147
dc.identifier.urihttps://hdl.handle.net/20.500.14981/50269
dc.identifier.volume35
dc.identifier.wos000259845500018
dc.language.isoeng
dc.publisherPERGAMON-ELSEVIER SCIENCE LTD
dc.relation.ispartofINTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER
dc.subjectcondensation
dc.subjecttwo-phase pressure drop
dc.subjectfriction factor
dc.subjectvertical downward flow
dc.subjectHFC-134a
dc.subjectequivalent Reynolds number model
dc.subjectHEAT-TRANSFER
dc.subjectPRESSURE-DROP
dc.subjectTUBE
dc.subjectMIXTURES
dc.subjectThermodynamics
dc.subjectMechanics
dc.titleTwo-phase friction factor in vertical downward flow in high mass flux region of refrigerant HFC-134a during condensation
dc.typeArticle
dspace.entity.typePublication