Yayın: PCA-ANN Based Algorithm for the Determination of Asymmetrical Network Failures of Network-Connected Induction Generators
Yükleniyor...
Tarih
Danışman
item.page.editor
Editör
Bölüm / Program
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
UNIV OSIJEK, TECH FAC
DOI
10.17559/tv-20171204220620
Türü
Özet
Presented in this study is a principal component analysis - artificial neural network based hybrid failure determination system that can make failure determination selectively and rapidly in asymmetrical external failures that might occur on the network side of a grid-connected induction generator. By creating asymmetrical external failures in the developed simulation model, analysis of noisy and unbalanced fluctuations that carry effects of positive, negative and zero sequence in currents were realized. The suggested model depends on entering data taken from the simulation into the artificial neural network model as a training data by being simplified with principal component analysis, in phase-phase, phase-ground and two phase-ground failures. The protection model makes correct classification with acceptable errors in case of above stated failures. However, in current fluctuations caused by sudden load changes and operation under an unbalanced load, it may remain insensitive by behaving selectively.
Tanım
Dergi veya Seri
TEHNICKI VJESNIK-TECHNICAL GAZETTE
ISSN