Yayın:
Effect of void fraction models on the two-phase friction factor of R134a during condensation in vertical downward flow in a smooth tube

dc.contributor.authorDalkilic, A. S.
dc.contributor.authorLaohalertdecha, S.
dc.contributor.authorWongwises, S.
dc.contributor.institutionauthorDALKILIÇ, Ahmet Selim
dc.date.accessioned2026-06-27T13:07:51Z
dc.date.issued2008
dc.description.abstractThe void fraction of R134a condensing inside a vertical smooth tube is experimentally investigated in this study. The vertical test section is a 0.5 m long countercurrent flow double tube heat exchanger with refrigerant flowing down the inner tube and cooling water flowing upward in the annulus. The inner tube is made from smooth copper tubing and has an 8.1 mm inner diameter. The test runs are done at an average saturated condensing temperature of 40 degrees C. The average qualities are between 0.8 and 0.99 while the mass fluxes are 300 kg m(-2) s(-1) and the heat fluxes are between 22 and 39.8 kW m(-2). The void fractions are indirectly determined using relevant measured data together with various void fraction models and correlations reported in the open literature. The friction factors obtained from various void fraction models and correlations are compared with each other and also with those determined from graphical information provided by Bergelin et al. The effect of void fraction alteration on the momentum pressure drop is also presented. (C) 2008 Elsevier Ltd. All rights reserved.en
dc.description.sponsorshipYildiz Technical University (Istanbul, Turkey)
dc.description.sponsorshipKing Mongkut's University of Technologhy Thonburi (KMUTT)
dc.description.sponsorshipThailand Research Fund (TRF)
dc.description.urihttps://doi.org/10.1016/j.icheatmasstransfer.2008.04.001
dc.identifier.doi10.1016/j.icheatmasstransfer.2008.04.001
dc.identifier.eissn1879-0178
dc.identifier.endpage927
dc.identifier.issn0735-1933
dc.identifier.issue8
dc.identifier.startpage921
dc.identifier.urihttps://hdl.handle.net/20.500.14981/50146
dc.identifier.volume35
dc.identifier.wos000259021000008
dc.language.isoeng
dc.publisherPERGAMON-ELSEVIER SCIENCE LTD
dc.relation.ispartofINTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER
dc.subjectheat transfer
dc.subjectvoid fraction
dc.subjectfriction factor
dc.subjectcondensation
dc.subjectdownward flow
dc.subjectR134a
dc.subjectPRESSURE-DROP
dc.subjectPREDICTION
dc.subjectGAS
dc.subjectThermodynamics
dc.subjectMechanics
dc.titleEffect of void fraction models on the two-phase friction factor of R134a during condensation in vertical downward flow in a smooth tube
dc.typeArticle
dspace.entity.typePublication
local.import.sourceWOS