dc.date.issued2018
dc.description.abstractThe traditional distribution networks are mostly radial. Radial networks are easy to implement and operate, but it introduces a great challenge concerning electricity supply reliability. In organized industrial zones, the unplanned energy interruptions can cost a lot, as industrial loads are always working. Consequently, distribution networks are mostly implemented as a ring network. The ring distribution network improves the electricity supply reliability. However, compared to the radial networks, the application of ring network introduces its own technical challenges such as increased short circuit current during the fault, difficulty in protection coordination, increased rating capacity of each equipment and increased investment cost. In this paper, the protection coordination technique that is used in an organized industrial zone will be discussed. In the ring distribution network, differential relays, which rely on communication between the protection relays, are used for the underground cable protection. To guarantee cable protection when communication is failed, an auxiliary protection by using directional overcurrent relays is used. In this paper, the protection coordination study for the GEBZE organized industrial zone, which is available in Istanbul, Turkey, is conducted by using state of the art methods. The results of the study are verified by applying to ABB relays, which are available on the organized industrial zone's site under study.en
dc.identifier.endpage1031
dc.identifier.isbn978-1-5386-5982-3
dc.identifier.issn2377-6897
dc.identifier.startpage1027
dc.identifier.urihttps://hdl.handle.net/20.500.14981/59812
dc.identifier.wos000457681100167
dc.language.isoeng
dc.publisherIEEE
dc.relation.conference7th International Conference on Renewable Energy Research and Applications (ICRERA)
dc.relation.ispartof2018 7TH INTERNATIONAL CONFERENCE ON RENEWABLE ENERGY RESEARCH AND APPLICATIONS (ICRERA)
dc.subjectDifferential protection
dc.subjectearth fault protection
dc.subjectorganized industrial zones
dc.subjectovercurrent protection
dc.subjectradial networks
dc.subjectring networks
dc.subjectScience & Technology - Other Topics
dc.subjectEnergy & Fuels
dc.subjectEngineering
dc.titleProtection Coordination Practices for Industrial Ring Distribution Network Case Study of Organized Industrial Zone (GEBZE, Turkey)