dc.description.abstractIn this study, a vertical ground source heat pump wall cooling system that belongs to the Yildiz Renewable Energy House at the Davutpasa Campus of Yildiz Technical University was studied both experimentally and theoretically. The principal objective was to perform a system analysis to determine the parameters that allow the energy usage of the cooling system to be as low as possible. For this reason, a system working in a low temperature regime was chosen. The examination includes energy and exergy analyses conducted during the period between 1 July and 30 September 2012, which is described as the Summer Session. By using the data that were collected on a per-second basis during these processes and conveyed to a MySQL database, The moments when the heat pump is activated were detected, and the Monthly Average Values were analyzed. Thus, a theoretical analysis was conducted for the Cooling Session and its correlations. These correlations were used in the energy and exergy analyses. According to the analysis results, the energy and exergy efficiencies of the entire system were found to be 74.85% and 29.90%, respectively, and the Wall Heating Cooling System panels calculated the heat with energy and exergy efficiencies of 90.29% and 80.4%, respectively. (C) 2015 Elsevier Ltd. All rights reserved.en
dc.description.urihttps://doi.org/10.1016/j.renene.2015.07.005
dc.identifier.doi10.1016/j.renene.2015.07.005
dc.identifier.endpage553
dc.identifier.issn0960-1481
dc.identifier.startpage540
dc.identifier.urihttps://hdl.handle.net/20.500.14981/54516
dc.identifier.volume85
dc.identifier.wos000363344800052
dc.language.isoeng
dc.publisherPERGAMON-ELSEVIER SCIENCE LTD
dc.relation.ispartofRENEWABLE ENERGY
dc.subjectCooling
dc.subjectEnergy
dc.subjectExergy
dc.subjectHeat pump
dc.subjectRenewable energy
dc.subjectWall cooling
dc.subjectEXPERIMENTAL PERFORMANCE ANALYSIS
dc.subjectEXERGY ANALYSIS
dc.subjectTHERMAL PERFORMANCE
dc.subjectSIMULATION
dc.subjectCOMFORT
dc.subjectWATER
dc.subjectPANEL
dc.subjectFLOOR
dc.subjectROOM
dc.subjectScience & Technology - Other Topics
dc.subjectEnergy & Fuels
dc.titleAnalysis of a wall cooling system using a heat pump
dc.typeArticle
dspace.entity.typePublication
local.import.sourceWOS

Dosyalar

Koleksiyonlar