dc.description.abstractThis study investigated the impact of two types of internal blinds on the indoor thermal environment of a highly glazed office room in Istanbul during summer. The research examined four configurations: (i) no blinds, (ii) roller blinds, (iii) layered roller blinds in night mode and (iv) layered roller blinds in day mode. Measurements of air velocity, average radiation temperature, air temperature and relative humidity were conducted to assess thermal comfort. The findings revealed that internal blinds significantly influence thermal comfort in radiantly cooled office spaces during summer. Without blinds, the indoor environment only met ISO 7730 comfort category C, with average predicted mean vote (PMV) and predicted percentage of dissatisfied (PPD) values of 0.6 and 12.5%, respectively. However, with internal blinds, comfort categories A and B were achieved, resulting in improved thermal comfort levels, with average PMV and PPD values ranging from 0.2 to 0.3 and 6% to 7.5%, respectively. Roller blinds, in particular, proved highly effective in enhancing thermal comfort and reducing mean radiant and indoor air temperatures in highly glazed radiant cooling offices. This demonstrated their energy-efficient potential for improving indoor thermal comfort.en
dc.description.sponsorshipBilimsel Arascedil
dc.description.sponsorshiptirma Projeleri Birimi, Yildiz Technical University
dc.description.sponsorshipYildiz Technical University
dc.description.urihttps://doi.org/10.1177/1420326x241243003
dc.identifier.doi10.1177/1420326x241243003
dc.identifier.eissn1423-0070
dc.identifier.endpage1414
dc.identifier.issn1420-326X
dc.identifier.issue8
dc.identifier.startpage1397
dc.identifier.urihttps://hdl.handle.net/20.500.14981/67753
dc.identifier.volume33
dc.identifier.wos001193818100001
dc.language.isoeng
dc.publisherSAGE PUBLICATIONS LTD
dc.relation.ispartofINDOOR AND BUILT ENVIRONMENT
dc.subjectIndoor thermal environment
dc.subjectRadiant cooling system
dc.subjectRoller blind
dc.subjectThe predicted mean vote and percentage of dissatisfied
dc.subjectGround source heat pump
dc.subjectVENETIAN BLIND
dc.subjectSOLAR-RADIATION
dc.subjectENERGY-CONSUMPTION
dc.subjectCOOLING SYSTEMS
dc.subjectGLASS WINDOW
dc.subjectBUILDINGS
dc.subjectTEMPERATURE
dc.subjectPERFORMANCE
dc.subjectSIMULATION
dc.subjectConstruction & Building Technology
dc.subjectEngineering
dc.subjectPublic, Environmental & Occupational Health
dc.titleThe effect of internal blinds on thermal comfort: An experimental analysis in an office room with radiant panels
dc.typeArticle
dspace.entity.typePublication
local.import.sourceWOS

Dosyalar

Koleksiyonlar