Measurement of the void fraction of R-134a flowing through a horizontal tube

Yükleniyor...
Küçük Resim

Tarih

Kurum Yazarları

Item type:Araştırmacı/Yazar,
DALKILIÇ, Ahmet Selim

Danışman

item.page.editor

Editör

Bölüm / Program

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

PERGAMON-ELSEVIER SCIENCE LTD

DOI

10.1016/j.icheatmasstransfer.2014.04.004

Türü

View PlumX Details

Araştırma Projeleri

Akademik Birimler

Dergi Sayısı

Özet

This experiment aims to measure the void fraction of R-134a refrigerant flowing through a horizontal tube, using a quick-closing valve and optical observation techniques. The tube is transparent, circular, 115 mm long with an inside 8 mm thick, and has two actuator ball valves installed at both ends. The experiment was conducted in conditions where vapor quality ranged from 1% to 82%, saturated temperature was from 23 to 30 degrees C, and mass flux was from 644 to 1455 kg/m(2) s. The results of the experiment indicate that raising the saturated temperature decreased the void fraction, whereas increasing mass flux had no significant effect on it. Moreover, results also show three flow regimes: intermittent, wavy, and annular. Each. flow regime led to different predicted void fractions. (C) 2014 Elsevier Ltd. All rights reserved.