Yayın:
Harmonic Analysis of Doubly Fed Induction Generator based Utility Interactive Wind Turbine Systems during Fault Conditions

Yükleniyor...
Küçük Resim

Tarih

Kurum Yazarları

Danışman

item.page.editor

Editör

Bölüm / Program

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

IEEE

DOI

Araştırma Projeleri

Akademik Birimler

Dergi Sayısı

Özet

This paper presents a detailed analysis of the doubly fed induction generator (DFIG) and converters by taking into account magnetic saturation of both DFIG and step-up transformer under symmetrical and asymmetrical faults. 2.5 MW DFIG is modeled through Finite Element Analysis software package and coupled with circuit and dynamic system simulators for accurate electromagnetic, drive and controller simulations. The effects of different type of utility grid faults on the DFIG rotor fluxes are analyzed and the FFT analysis of the rotor fluxes is carried to correlate the harmonic content of the rotor fluxes with the fault types. The study would provide guidance in developing advanced control and protection techniques for the DFIG system during fault conditions. The simulation results are verified with the 7.5 Hp experimental DFIG system.