Yayın:
The Influence of Voltage and Frequency Variations on Insulation Quality of a High Voltage Cable

dc.contributor.authorKocatepe, Celal
dc.contributor.authorKumru, Celal Fadil
dc.contributor.authorAyaz, Ramazan
dc.contributor.authorArikan, Oktay
dc.contributor.authorAkca, Hakan
dc.contributor.institutionauthorAYAZ, Ramazan
dc.contributor.institutionauthorARIKAN, Oktay
dc.date.accessioned2026-06-27T13:27:49Z
dc.date.issued2013
dc.description.abstractInsulation quality issue has had a significant place in high voltage systems for long years. Especially for high voltage cables, which is one of the most crucial elements in power systems, the measurements of dissipation factor or tan delta has a great importance on the insulation life time. Besides, when the power system parameters such as frequency and voltage level are not steady, tan delta measurement values will also be changed. Therefore, tan delta and dielectric loss measurement should be realized in case of unsteady power system conditions to get more exact results. In this study, tan delta measurement of a 20,1/34,5 kV, single core high voltage cable is carried out. By changing the frequency and voltage level, dissipation factor, capacitance (C-s), insulation resistance (R-s) and dielectric losses (P-k) measurement values are obtained.en
dc.identifier.endpage968
dc.identifier.isbn978-1-4673-2232-4; 978-1-4673-2230-0
dc.identifier.startpage964
dc.identifier.urihttps://hdl.handle.net/20.500.14981/52862
dc.identifier.wos000343135600140
dc.language.isoeng
dc.publisherIEEE
dc.relation.conferenceIEEE EUROCON Conference
dc.relation.ispartof2013 IEEE EUROCON
dc.subjectTan delta
dc.subjectdielectric loss
dc.subjectHigh Voltage (HV) cable
dc.subjectHV measurement
dc.subjectXLPE cable
dc.subjectComputer Science
dc.subjectTelecommunications
dc.titleThe Influence of Voltage and Frequency Variations on Insulation Quality of a High Voltage Cable