Yayın:
Experimental study on evaporative heat transfer and pressure drop of R-134a in a horizontal dimpled tube

dc.contributor.authorAroonrat, Kanit
dc.contributor.authorAhn, Ho Seon
dc.contributor.authorJerng, Dong-Wook
dc.contributor.authorAsirvatham, Lazarus Godson
dc.contributor.authorDalkilic, Ahmet Selim
dc.contributor.authorMahian, Omid
dc.contributor.authorWongwises, Somchai
dc.date.accessioned2026-06-27T14:19:46Z
dc.date.issued2019
dc.description.abstractThe heat transfer and pressure drop characteristics of R-134a during evaporation in smooth and dimpled tubes are experimentally examined. All test sections used in this study are double-tube heat exchangers, where the hot water in an annulus transfers its heat to R-134a in the inner tube. The experiments are conducted in a mass flux range of 300-500 kg/m(2) s, heat flux range of 20-30 kW/m(2), and evaporating temperature range of 7-13 degrees C. Smooth and dimpled tubes with a length of 1500 mm and an inner diameter of 8.1 mm are tested. The results indicate that the tube with protrusions enhance the heat transfer up to 70% along with a pressure drop increase up to 587% over the smooth tube. The effects of relevant parameters on heat transfer and pressure drop are explored. In this experiment, the heat transfer enhancement factor falls in the range of 1.26-1.7, while the pressure drop penalty factor fluctuates between 3.78 and 6.87. In addition, the efficiency index is applied to estimate the performance of dimpled tube. It is found that all efficiency index values are in the range of 0.18-0.42. (C) 2019 Elsevier Ltd. All rights reserved.en
dc.description.sponsorshipResearch Chair Grant National Science and Technology Development Agency (NSTDA)
dc.description.sponsorshipKing Mongkut's University of Technology Thonburi through the KMUTT 55th Anniversary Commemorative Fund
dc.description.urihttps://doi.org/10.1016/j.ijheatmasstransfer.2019.118688
dc.identifier.doi10.1016/j.ijheatmasstransfer.2019.118688
dc.identifier.eissn1879-2189
dc.identifier.issn0017-9310
dc.identifier.urihttps://hdl.handle.net/20.500.14981/59325
dc.identifier.volume144
dc.identifier.wos000494883300102
dc.language.isoeng
dc.publisherPERGAMON-ELSEVIER SCIENCE LTD
dc.relation.ispartofINTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
dc.subjectEvaporation
dc.subjectHeat transfer
dc.subjectPressure drop
dc.subjectDimpled tube
dc.subjectMICRO-FIN TUBES
dc.subjectHIGH-MASS FLUX
dc.subjectGENERAL CORRELATION
dc.subjectEMPIRICAL CORRELATIONS
dc.subjectTRANSFER COEFFICIENTS
dc.subjectNUMERICAL CORRELATION
dc.subjectCONDENSATION
dc.subjectSMOOTH
dc.subjectFLOW
dc.subjectR-600A
dc.subjectThermodynamics
dc.subjectEngineering
dc.subjectMechanics
dc.titleExperimental study on evaporative heat transfer and pressure drop of R-134a in a horizontal dimpled tube